If the power meter is collecting data, and the comms are lost for a period of time, how do I get htat data off the data off the meter that the BMS didn't record?

There are two ways to retrieve data if there's an interruption in communication (BACnet/Modbus).

1. Over BACnet, access trending objects. 

*Note - this is not possible in Modbus.

2. Going thru the web portal on your PC/laptop over USB or Ethernet if the IP address is known, 

  • Go to the Power Analytics tab
  • Odometer
  • Select the load(s) of interest
  • For each load in odometer page
  • Hit EXPORT ALL to generate a .csv file. 

*This is very time consuming if there are many loads.